Humanoid Control Prime is the bimanual humanoid. The waist is dropped this version (rigid torso, no waist drives), leaving 14 actuated DoF — 7 per arm. What makes Prime different from Lite is that those 14 joints live on two different buses, driven by two different actuator families, yet present a single uniform MIT command surface to one controller_manager. This page is the "why" layer for the whole Prime bringup: the topology, how each family realizes impedance, the exact SI-to-actuator conversions, the per-mode PD values, and the DC-sync, switch-latency, and startup behaviors we had to solve.

Topology — 14 DoF on two buses

Each arm has the same 7 joints. Five are eRob (ZeroErr CiA402 servos on EtherCAT, through the IgH master); two — the distal wrist roll/pitch — are Sito (TA40-50 MIT motors on SocketCAN).

Joint (per arm)FamilyBusAddress
shoulder_pitcheRobEtherCAT (master 0)ring pos 0 / 5
shoulder_rolleRobEtherCATring pos 1 / 6
shoulder_yaweRobEtherCATring pos 2 / 7
elbow_pitcheRobEtherCATring pos 3 / 8
wrist_rollSitoSocketCAN can2id 22 (L) / 38 (R)
wrist_pitchSitoSocketCAN can2id 23 (L) / 39 (R)
wrist_yaweRobEtherCATring pos 4 / 9

So the EtherCAT ring carries 10 eRob (positions 0-9, left arm 0-4, right arm 5-9) and the CAN bus carries 4 Sito wrists (ids 0x16/0x17/0x26/0x27). All Prime eRob are 50:1 gear. The single source of truth for this mapping is humanoid_bringup_prime/config/prime_hardware.yaml (buses, joints.all_joints, joints.erob_slaves, joints.mit_joints); the per-joint bus assignment is emitted by prime_description (robots/prime_dummy/xacro/prime_dummy.ros2_control.xacro).

Note the kinematic order in all_joints (shoulder pitch/roll/yaw, elbow, wrist roll/pitch/yaw) is not the ring orderwrist_yaw is eRob position 4/9 even though it sits distal of the two Sito wrists. Controllers bind to the flat 14-joint all_joints list regardless of which bus carries each joint.

Which eRob model, and why it matters a little

Two eRob models appear on Prime, distinguished only by their motor torque constant (read each joint's model off its label; see the eRob manual §25.2):

Model / versionKt (Nm/mA, at motor)
eRob70 V4_MC20.132e-3 (the code default)
eRob80 V5_MC20.134e-3 (≈ 1.5% higher)

The 1.5% Kt difference is negligible in practice; the gear ratio would be the real lever, but every Prime eRob is 50:1, so a single conversion serves all of them. humanoid_bringup_prime/config/prime_hardware.yaml can still override Kt/gear per joint (joints.erob_kt / joints.erob_gear) if a model ever differs.

One controller_manager, two ros2_control blocks

real.launch.py expands the xacro with use_fake_hardware:=false use_sim:=false, which emits two concurrent ros2_control blocksPrimeEtherCATSide (ethercat_driver/EthercatDriver, the 10 eRob) and PrimeSitoCAN (humanoid_devices_sito/SitoSystem, the 4 Sito wrists). One controller_manager runs them together and exposes a flat 14-joint list to the mode controllers. The sim path (mujoco.launch.py) collapses both into one MujocoSystem block but presents the identical 14 joints, so the shared controllers run unchanged.

Two bringup details are load-bearing:

  • control_frequency must equal the CM update_rate (50 Hz). The eRob DC SYNC0 cycle is driven from the controller_manager's update() loop, not a separate thread. If control_frequency is higher than update_rate, SYNC0 fires more often than process-data frames arrive, the distributed clock can't lock, and the drives fault. real.launch.py reads update_rate out of the controllers YAML and derives control_frequency from it so they cannot diverge.
  • Spawners are sequenced (joint_state_broadcasterzero_torque_controller → the inactive mode controllers). The eRob activation takes tens of seconds (see Startup time); running the spawners concurrently makes them contend on the spawner's hard-coded 20 s file lock, time out, and collide. Chaining them on process-exit means each acquires the lock alone.

Two actuator families, two ways to realize impedance

Both families expose the same five MIT command interfaces (position, velocity, effort, stiffness, damping), but they implement the τ = Kp·(q_cmd − q) + Kd·(q̇_cmd − q̇) + τ_ff law very differently — and that difference is the heart of the Prime control story.

Sito: native MIT over CAN

The Sito firmware runs the MIT law directly. The host sends the desired position, velocity, and feedforward torque in a command frame, and Kp/Kd in a separate gains frame. Conversions (in humanoid_devices/humanoid_devices_sito/include/humanoid_devices_sito/sito_protocol.hpp, TA40-50):

position_counts = q_cmd  · 65536 / (2π)        # 16-bit encoder, MOTOR side
velocity_counts = q̇_cmd · 65536 / (2π)
ff_current[mA] = τ_ff / (Kt · gear) # Kt = 9e-5 Nm/mA, gear = 51
Kp_sent = kp / 688.58 # Nm/rad per firmware Kp unit
Kd_sent = kd / 1.125 # Nm·s/rad per firmware Kd unit

The 688.58 / 1.125 divisors are a measured calibration of the firmware's per-unit physical effect at the joint output. An earlier version of the code used 500 / 0.5, which silently ran the wrists about 1.38x too stiff and 2.25x over-damped; the measured divisors fix that. (Because that section of the source derivation is iterative, reconfirm with a torque measurement if you need precision.)

eRob: MIT-in-CSP (impedance emulated by loop gains)

The eRob has no per-tick stiffness/damping interface. It runs CSP (Cyclic Synchronous Position, mode 8): the controller commands a target position every tick, and the joint's impedance is the drive's internal position and velocity loop gains. A cascaded position→velocity loop linearizes to kp = Kpos · Kvel and kd = Kvel, which is why stiffness is expressed through the loop gains.

The gains are manufacturer CoE objects, reachable only by acyclic SDO (they are not PDO-mappable, so they cannot be a per-tick command interface):

ObjectRole
0x2382:01position loop gain (pos_reg)
0x2381:01velocity loop gain (vel_reg)
0x2381:02velocity loop integral (held at 0 for clean impedance)
0x2383"Bus Regulation of PID" gate — 1 = use bus-written gains, 0 = factory

The SI-to-register conversion (humanoid_bringup_prime/scripts/erob_impedance_manager.py, erob_gains()), validated exactly against the ZeroErr derivation:

vel_reg (0x2381:01) = kd / 0.1063   ≈ 9.41 · kd       # cD = 0.1063 Nm·s/rad per LSB
pos_reg (0x2382:01) = (kp / kd) · 51.47 # cP = 0.01943, ratio only
integral (0x2381:02) = 0

Consequences worth remembering:

  • kd > 0 is required for any stiffness. Because pos_reg is proportional to kp/kd, a kd of 0 collapses both registers to 0 (true limp / zero torque).
  • Only vel_reg depends on Kt and gear. The kp/kd ratio that sets pos_reg is model-independent, so the eRob80 vs eRob70 difference touches only the damping register.
  • Feedback is gear-independent. Position and velocity are read from the 19-bit output encoder, so a wrong gear/model would only mis-scale the impedance magnitude, never the position tracking.

The realized-vs-nominal caveat (transmission efficiency)

Load tests showed the eRob realizes roughly 0.7x the nominal stiffness. The clean explanation is that the manual's output-torque relation is joint Kt = motor Kt · gear · transmission_efficiency, and the conversion above omits the efficiency term (harmonic drives are ~0.7-0.85 efficient). The manager exposes an optional torque_efficiency parameter (default 1.0 = off); setting it to the measured realized/nominal ratio compensates the loss. It is applied to vel_reg only, which provably corrects both the realized kp and kd while leaving pos_reg (the ratio) untouched.

Per-mode PD values

The mode controllers (five-mode FSM) set these per mode. The eRob per-mode gains live in erob_impedance_manager's mode_kp/mode_kd; the Sito gains come from the active controller's stiffness/damping.

Modekp (Nm/rad)kd (Nm·s/rad)Notes
ZERO_TORQUE00True limp on both families
DAMPING06Uniform across eRob + Sito (compliant fail-safe)
STANDBY202Position hold; ramps in over the entry trajectory
LOCOMOTION202 (eRob, fixed)Sito follow the policy's per-tick gains
REMOTE202 (eRob, fixed)Sito follow the per-tick remote command

Key asymmetry: the eRob impedance is per-mode only. SDO is acyclic and slow, so the manager cannot retrack a per-tick varying stiffness — it writes a fixed impedance on each mode change. In LOCOMOTION/REMOTE the four Sito wrists honor the policy's per-tick Kp/Kd, but the ten eRob arm joints hold the fixed mode impedance and track position in CSP.

The eRob impedance manager

humanoid_bringup_prime/scripts/erob_impedance_manager.py is the bridge between the mode FSM and the eRob loop gains. It subscribes to /control_mode and, on each transition, converts that mode's (kp, kd) to loop-gain registers and writes them over the EtherLab ethercat download CLI. (It uses the CLI, not the in-process ethercat_manager SDO service, because the conda libethercat is version-mismatched against the running kernel master.)

The one rule that keeps bringup healthy:

No SDO touches the bus until /prime/joint_states is flowing. The joint_state_broadcaster only activates once every slave is fully OP, so that topic is the "hardware is up" signal. Mailbox SDO traffic during the staged DC activation disrupts the cyclic exchange and faults a slave with 0xA000 (EtherCAT communication error). The manager therefore stays entirely off the bus until the robot is up, then arms the gate (0x2383=1) and writes the first mode's gains. It resets the gate to 0 on exit so the next bringup activates with factory (stiff) gains.

Per-joint Kt/gear and the scalar torque_efficiency are parameters, wired from prime_hardware.yaml.

Two things we solved

PD-switch latency (3.6 s → 0.46 s)

Symptom: switching modes (e.g. DAMPING ↔ STANDBY) propagated visibly across the arms — the left shoulder responded immediately, the right arm seconds later.

Mechanism: in OP each CoE SDO transfer is cycle-gated — the master advances the SDO state machine roughly once per 50 Hz cycle, so one object takes ~120 ms (~6 cycles). A mode switch writes 3 objects to 10 slaves = 30 SDOs, and the manager did them strictly in ring order, so the total was ~3.6 s with the tail-of-ring (right arm) carrying the full cumulative delay.

Fix: the IgH master pipelines outstanding mailbox transfers across slaves, so issuing the per-slave writes concurrently (one worker per slave) collapses the wall-clock from sum-of-slaves to roughly one slave's time — measured ~0.46 s, all slaves within ~40 ms of each other. Controlled by the parallel_sdo parameter (default on); set it false to reproduce the sequential baseline.

Startup time (70 s → 13.6 s)

Symptom: bringup took ~70 s and logged ~7 transient 0xA000 fault/recover cycles before stabilizing.

Mechanism: a slave reaches EtherCAT OP only after the master's DC drift compensation converges, which is cycle-count bound. The ICube ethercat_driver's on_activate bring-up loop paced its update() at control_frequency (50 Hz), so convergence took ~7 s per slave (the domain working-counter climbed one slave at a time, ~7 s apart). The 0xA000 faults were collateral: each newly-joining slave briefly glitched the domain and starved the others' output-watchdog.

Fix: a small patch runs the bring-up loop at 1 kHz, independent of control_frequency. DC converges ~5x faster and the watchdog stays fed, so bringup drops to ~13.6 s with zero faults — and there is no steady-state change (DC SYNC0 still runs at control_frequency, and the CM read/write loop takes over at update_rate once activation returns). The patch is a local modification to the ICube ethercat_driver_ros2 that bar.repos pins (ethercat_driver/src/ethercat_driver.cpp); to survive a fresh vcs import it must land in a Berkeley fork that bar.repos then pins (TODO).

Fault / status reference

The CiA402 statusword and eRob error codes you will actually see on Prime:

CodeMeaning
statusword 5687Operation Enabled (healthy, running)
statusword 4616Fault state — on Prime almost always the DC-sync / comms family
error 0xA000EtherCAT communication error (see startup + impedance-manager notes above)
error 0x8500Position error exceeds limit
error 0x8400Velocity error exceeds limit
error 0x8130CAN heartbeat error

Read the live error code with ethercat upload -pN 0x603F 0 and the stored history with 0x1003. Symptom-first entries are on the Troubleshooting page.